Addressable 230 V centrally supplied Emergency / Exit Light. The package includes the luminaire, and a rotatable sign.
Teknoware Combo is a combination light, which can be used as both an emergency and emergency exit light. Fitted with a rotatable sign, Combo can show the direction arrow pointing up, down, left and right. When using Combo as an emergency light, the sign is not installed. Combo's versatility makes it a cost-effective light and the ideal choice when you want a single fixture for your entire property's needs.
Product Code | YB151WK120 |
Feature | Intelligent Controller, Tapsa Control |
Mounting (standard) | wall, ceiling, surface, recess |
Customs Code | 94056080 |
GTIN Code | 6438045024707 |
ETIM Product Class | EC001957 |
Length | 270 mm |
Width | 147 mm |
Height | 60 mm |
Weight | 0.55 kg |
Max Input Power VA | 5,7 VA |
Max Input Power W | 3,4 W |
Nominal Supply Voltage | 220-240 V, 50/60 Hz AC, DC |
Protection Class | II |
IP Class | IP40 |
Temperature Range Min - Max | -30…+50 °C |
Glow Wire Test of Plastic Materials | 650 °C |
Viewing Distance | 25 m |
Light Source | LED |
Body Material | plastic |
Colour | RAL9003 |
Electrical Installation | 2/3 x 2,5 mm² |
Luminous Flux | 170 lm |
Emergency lighting for escape routes (ceiling mounting)
- Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
- Level of measurement 0,02 m, measurement result with battery operation.
- R1 distance from wall (X axis)
- R2 installation distance between lights (X axis)
- R4 distance from wall (Y axis)
YB151WK120
Mounting height (m) | Below the light lux | R1 (m) | R2 (m) | R4 (m) |
---|---|---|---|---|
1 lux | 1 lux | 1 lux | ||
2,5 | 7 | 3 | 8 | 1 |
3 | 5 | 3 | 8.5 | 1 |
4 | 2.5 | 3 | 9.5 | 1 |
Emergency lighting for open areas (ceiling mounting)
- Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
- Level of measurement 0,02 m, measurement result with battery operation.
- R1 distance from wall (X axis)
- R2 installation distance between lights (X axis)
- R3 installation distance between lights (Y axis)
- R4 distance from wall (Y axis)
YB151WK120
Mounting height (m) | Below the light lux | R1 (m) | R2 (m) | R3 (m) | R4 (m) |
---|---|---|---|---|---|
0,5 lux | 0,5 lux | 0,5 lux | 0,5 lux | ||
2,5 | 7 | 3.5 | 7 | 7 | 3.5 |
3 | 5 | 3.5 | 7 | 7 | 3.5 |
4 | 2.5 | 3.5 | 7.5 | 7.5 | 3.5 |
6 | 1.2 | 4 | 8 | 8 | 4 |
Optional accessories:
Optional Mounting Accessories for Emergency Exit Lights

Product Code | Product Name | Compatible Product Groups | Add to offer basket |
---|---|---|---|
TWTB101 | Combo recess mounting frame TWTB101 | Combo Emergency / Exit Light, Combo Emergency / Exit Light | |
TWTB103 | Combo flag bracket TWTB103 | Combo Emergency / Exit Light, Combo Emergency / Exit Light | |
TWTB104 | Combo ceiling bracket TWTB104 | Combo Emergency / Exit Light, Combo Emergency / Exit Light | |
TWTB105 | Combo suspension bracket TWTB105 | Combo Emergency / Exit Light, Combo Emergency / Exit Light |