Combo emergency light and emergency exit light TWTB153WM

220-240 V 50/60 Hz AC
3h
LED
IP 40
25 m
RAL 9003
850 °C
EN 1838
EN 60598-2-22

Self-contained Emergency / Exit Light with 3 h Battery and Lumi Test Self-testing.

Teknoware Combo is a combination light, which can be used as both an emergency and emergency exit light. Fitted with a rotatable sign, Combo can show the direction arrow pointing up, down, left and right. When using Combo as an emergency light, the sign is not installed. Combo's versatility makes it a cost-effective light and the ideal choice when you want a single fixture for your entire property's needs.

Product CodeTWTB153WM
FeatureLumi Test
Mounting (standard)wall, ceiling, surface, recess
Customs Code94056080
GTIN Code6438045024622
ETIM Product ClassEC001957
Length265 mm
Width137 mm
Height53 mm
Weight0.45 kg
Backup3 h
Max Input Power VA8 VA
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassII
IP ClassIP40
Temperature Range Min - Max-5...+35 °C
Glow Wire Test of Plastic Materials850 °C
Viewing Distance25 m
Light SourceLED
Body Materialplastic
ColourRAL9003
Electrical Installation2/3 x 2,5 mm²
Luminous Flux170 lm

Emergency lighting for escape routes (ceiling mounting)

  • Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R4 R2 X h
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R4 distance from wall (Y axis)

TWTB153WM

Mounting height (m)Below the light luxR1 (m)R2 (m)R4 (m)
1 lux1 lux1 lux
2,57381
3538.51
42.539.51

Emergency lighting for open areas (ceiling mounting)

  • Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R3 R2 X h R4
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R3 installation distance between lights (Y axis)
  • R4 distance from wall (Y axis)

TWTB153WM

Mounting height (m)Below the light luxR1 (m)R2 (m)R3 (m)R4 (m)
0,5 lux0,5 lux0,5 lux0,5 lux
2,573.5773.5
353.5773.5
42.53.57.57.53.5
61.24884

Optional accessories:

Optional Mounting Accessories for Emergency Exit Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TWTB101Combo recess mounting frame TWTB101Combo Emergency / Exit Light, Combo Emergency / Exit Light
TWTB103Combo flag bracket TWTB103Combo Emergency / Exit Light, Combo Emergency / Exit Light
TWTB104Combo ceiling bracket TWTB104Combo Emergency / Exit Light, Combo Emergency / Exit Light
TWTB105Combo suspension bracket TWTB105Combo Emergency / Exit Light, Combo Emergency / Exit Light