Zonespot II Midbay LED Emergency Light TWS9392WA

220-240 V 50/60 Hz AC
1h
LED
IP 44
RAL 9003
850 °C
EN 60598-2-22

Self-contained ESCAP Emergency Light with 1 h Super Capacitor and Wireless Central Monitoring

Teknoware's Zonespot II Midbay is a surface mounted emergency light for open areas. TWT93/TWS93 model is suitable for areas with 2-8 meter's height. High Output version TWT9356WK can be mounted in up to 14 meter's height. Zonespot II Midbay is easy and fast to install thanks to a separate mounting base, into which the power supply is also connected.

Zonespot II Midbay takes advantage of the latest LED technology. Its optics are designed to provide a broad, uniform lighting pattern, which illuminates the open areas effectively. Zonespot II is also suitable for damp locations.

Product CodeTWS9392WA
FeatureAalto Control, Escap, Lumi Test
Mounting (standard)surface
Mounting (optional)pendel
Customs Code94056080
GTIN Code6438045019048
ETIM Product ClassEC001957
Length180 mm
Width180 mm
Height50 mm
Weight0,9 kg
Backup1 h
Max Input Power VA3 VA
Nominal Supply Voltage220-240 V, 50/60 Hz AC
Protection ClassII
IP ClassIP44
Temperature Range Min - Max-25...+35 °C
Glow Wire Test of Plastic Materials850 °C
Light SourceLED
Body Materialplastic
ColourRAL9003
Electrical Installation2/3 x 2,5 mm²
Luminous Flux60 lm

Emergency lighting for escape routes (ceiling mounting)

  • Table of 1 lux for escape routes in the middle line according to the norm EN 1838.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R4 R2 X h
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R4 distance from wall (Y axis)

TWS9392WA

Mounting height (m)Below the light luxR1 (m)R2 (m)R4 (m)
1 lux1 lux1 lux
2,58,5252
36
43,5363
61,5373

Emergency lighting for open areas (ceiling mounting)

  • Table of 0,5 lux for open areas according to the norm EN 1838, 0,5 m edge district is considered in the table.
  • Level of measurement 0,02 m, measurement result with battery operation.
Y R1 R3 R2 X h R4
  • R1 distance from wall (X axis)
  • R2 installation distance between lights (X axis)
  • R3 installation distance between lights (Y axis)
  • R4 distance from wall (Y axis)

TWS9392WA

Mounting height (m)Below the light luxR1 (m)R2 (m)R3 (m)R4 (m)
0,5 lux0,5 lux0,5 lux0,5 lux
2,58,52442
3624,54,52
43,52552
61,53663

Optional accessories:

Shock Protecting Covers for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TW77507BShock protecting cover TW77507BESC 10 Emergency Exit Lights, ESC 80 Emergency Exit Lights

Optional Mounting Accessories for Emergency Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TW77504FSuspension bracket TW77504FLinespot II Lowbay, Surface-Mounted Emergency Lights, Zonespot II Lowbay, Surface-Mounted Emergency Lights, Zonespot II Midbay, Surface-Mounted Emergency Lights, Linespot II Midbay, Surface-Mounted Emergency Lights, Zonespot II Highbay, Surface-Mounted Emergency Lights

You may also be interested in these products:

Self-Contained ESCAP Emergency Exit Lights with Super Capacitor and Wireless Central Monitoring

Product CodeNominal Supply VoltagePictogramPictogram InfoBackup (h)Add to offer basket
TWS9092WA220-240 V, 50/60 Hz AC2-sided, 25 m1
TWS8092WA220-240 V, 50/60 Hz AC2-sided, 20/26/30 m1

Wireless Aalto Control Central Monitoring for Self-Contained Emergency and Exit Lights

Product CodeProduct NameCompatible Product GroupsAdd to offer basket
TST5104CAalto Control V4 PC Software TST5104CSelf-Contained ESCAP Emergency Lights with Super Capacitor and Wireless Central Monitoring, Self-Contained Emergency Lights with Battery and Wireless Central Monitoring, Self-Contained ESCAP Emergency Exit Lights with Super Capacitor and Wireless Central Monitoring, Self-Contained Emergency Exit Lights with Battery and Wireless Central Monitoring

Information and offers on Zonespot II Midbay LED Emergency Light TWS9392WA

Installation video of Zonespot II and Linespot II Lowbay Midbay